Interbus slave terminal EL6740-0010
Status LEDs
Fieldbus signal
input
Fieldbus signal
output
Top view

EL6740-0010 | Interbus slave terminal

Technical data EL6740-0010
Technology Interbus slave terminal
Fieldbus Interbus, max. 400 m between 2 stations at 500 kbit/s
Number of fieldbus channels 1
Data transfer rates 500 kbits, 2 Mbits (default)
Interfaces 2 x D-sub plug, 9-pin, plug and socket with screening and vibration lock
Max. number of bytes fieldbus 32 word input and 32 word output
Hardware diagnosis status LEDs
Distributed clocks
Type of connection only remote bus
Current consumption power contacts
Current consumption E-bus typ. 450 mA
Special features status LEDs
Weight approx. 80 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/see documentation
Approvals CE, UL, Ex
System  